Most three-phase motor starters are built from two devices working as a pair: a contactor that switches the motor on and off, and a thermal overload relay that protects it while it runs. If you are choosing an AC contactor for a new starter, or replacing the one in a burnt panel, the selection comes down to a few numbers on the motor nameplate, not a guess from the motor frame size. The short answer: pick a contactor whose AC-3 current rating is at least equal to the motor’s full-load current (FLC), then pair it with an overload relay whose adjustable range covers that same current and set the dial to the nameplate value. This guide walks through the sizing steps, a practical rating table, and the mistakes that cause starters to fail early.
What Is a Contactor for a Motor Starter?
A motor starter is the assembly that starts, stops, and protects a motor. In the most common arrangement, a direct-on-line (DOL) starter, a single contactor connects the motor straight to the supply when its coil is energised, and the overload relay sits between the contactor output and the motor to watch the current flowing to it.
- The contactor does the switching. It closes the main power contacts when the coil is energised and opens them when the coil is de-energised, which gives you remote and automatic control via push buttons, timers, thermostats, or a PLC.
- The overload relay does the protecting. It is connected in series with the motor and trips the starter circuit if the current stays above the motor’s rated value long enough to heat the motor.
- Upstream protection (a fuse, MCB, or MCCB) covers short circuits. It is a separate job from motor overload protection, which is why it is not covered by the contactor either.
So when someone says “contactor for a motor starter”, they usually mean the main switching device inside a DOL, reversing, or star-delta starter — sized for motor duty, not for general switching.


A Contactor Switches; It Does Not Protect the Motor
This boundary is where many starter faults start. A contactor is designed to make and break the circuit under defined conditions — for motor duty, it must close against the motor’s starting inrush current (typically six to eight times FLC for a short time) and break the running current when the motor is switched off. It is not designed to interrupt a sustained overload, and its contacts will erode quickly if they are forced to do so.
The thermal overload relay exists precisely because of that. It lets normal starting current pass, but if the motor runs overloaded, loses a phase, or is mechanically stalled, the relay heats up and opens its NC contact in the control circuit, which drops the contactor coil and stops the motor. For the same reason, a circuit breaker that protects the wiring is not a substitute: breakers and fuses are sized for short-circuit currents, not for the moderate, long-lasting overloads that damage motor windings. If you want the full division of duties, our comparison of a contactor vs circuit breaker explains which device protects what.
How to Choose a Contactor for a Motor Starter
Follow these steps in order. The complete logic behind each one is covered in our guide on how to size and select a contactor; here is the motor-starter version.
- Get the motor full-load current from the nameplate. This is the number everything else hangs on. For a rough cross-check on a 400V three-phase motor you can estimate about 1.9-2A per kW, but always use the nameplate FLC — motor design, efficiency class, and voltage all change the real value.
- Confirm the utilization category. Standard motor starting and running is AC-3 duty under IEC 60947-4-1. Reversing, plugging, and inching are AC-4, which is far more severe and may need a bigger frame. If the categories are new to you, our explainer on AC-1 to AC-4 utilization categories shows what each one means for contact selection.
- Size the contactor by its AC-3 rating, not its AC-1 rating. Choose a frame whose AC-3 current rating is at least equal to the motor FLC. Adding 10-25% margin is common practice to cover voltage dips, ambient heat, and duty variations; when in doubt between two frames, take the next size up.
- Match the coil voltage to the control circuit, not the motor. A 400V motor does not imply a 400V coil. PLC panels commonly use 24V DC; traditional panels use 110V, 220V, or 230V AC control transformers. Getting this wrong is one of the most frequent ordering errors — see our guide to contactor coil voltage before you order.
- Check poles and auxiliary contacts. Use a 3-pole contactor for a three-phase motor, and confirm how many NO/NC auxiliary contacts you need for the hold-in circuit, indicators, or interlocking.
- Account for the environment. In a hot enclosure, derate the contactor or move up a frame. High altitude and frequent duty cycles also reduce the usable rating.
Contactor Sizing Table for Common Motors
The table below gives typical values for three-phase motors at 400V, 50Hz. Currents are approximations for planning; always confirm against the actual motor nameplate before buying.
| Motor power (kW) | Typical FLC at 400V (A) | Minimum AC-3 contactor frame (A) |
|---|---|---|
| 1.5 | 3.4 | 9 |
| 2.2 | 4.8 | 9 |
| 4 | 8.2 | 12 |
| 5.5 | 11 | 18 |
| 7.5 | 15 | 18-25 |
| 11 | 21 | 25-32 |
| 15 | 28 | 32-40 |
| 18.5 | 34 | 40 |
| 22 | 41 | 50 |
| 30 | 57 | 65 |
| 37 | 70 | 80 |
| 45 | 84 | 95 |
| 55 | 103 | 115 |
The same motor at 380V draws slightly more current, and at 415V slightly less, so re-check the current whenever the local supply differs from 400V. Large-frame motor-duty contactors such as the CJX2-F series cover the heavier end of this range with the AC-3 ratings printed for each frame.
Match the Overload Relay to the Contactor
The overload relay is chosen independently of the contactor frame, even though the two are mounted together and often supplied as a matched set. Its job is to protect the motor, so it is selected from the motor FLC, not from the contactor rating.
- Pick a relay whose adjustable range brackets the FLC. If the motor draws 15A, choose a relay adjustable from roughly 12-18A rather than one pegged at its top or bottom limit; setting near mid-range leaves room to fine-tune in the field.
- Set the dial to the motor nameplate FLC. That is the baseline. Depending on the local code and the motor service factor, the setting may be permitted up to about 115-125% of FLC, but it should never be set to the breaker rating or the contactor rating.
- Choose the trip class for the starting time. Class 10 suits normal motors that start in a few seconds; Class 20 and Class 30 are for high-inertia loads such as fans and flywheels that take longer to start and would trip a Class 10 relay during every start.
- Decide the reset mode. Manual reset is safer for attended machines that should not restart by themselves after a trip; automatic reset suits remotely supervised or inaccessible installations.
- For three-phase motors, prefer a phase-loss sensitive relay. A relay with differential (phase-loss) protection detects when one supply phase drops and trips the motor before it overheats on single-phase running.
If you want to see how the relay and contactor behave together when something goes wrong, our contactor troubleshooting guide covers the symptoms that show up when either device is wrongly matched.


Reversing Starters Need Mechanically Interlocked Contactors
A reversing starter uses two contactors, one for each direction, because swapping any two supply phases reverses the motor. The danger is that if both contactors close at the same time, the phases are short-circuited through the two contactors. Two protections are standard: electrical interlocking through the auxiliary contacts, and mechanical interlocking, where a physical linkage prevents both armatures from closing even if the coils are energised together by a fault or a wiring error.
For this duty you need pairs of contactors built or supplied as interlocked units, such as the CJX2-F400 mechanical interlocking contactor, which is designed for reversing and changeover applications up to the heavier motor sizes. The mechanical interlock is the layer that keeps working when the control wiring does not.
Common Mistakes When Sizing a Starter Contactor
- Sizing from motor power with a fixed multiplier. kW alone cannot give you the current without voltage, power factor, and efficiency. Always convert kW to current with the correct voltage, then verify against the nameplate.
- Using the AC-1 rating instead of the AC-3 rating. The resistive-load (AC-1) figure is higher than the motor-duty (AC-3) figure on the same contactor, so sizing by AC-1 leaves the contacts undersized for starting duty.
- Ordering the coil voltage to match the motor voltage. The coil must match the control circuit supply, not the motor supply.
- Omitting the overload relay because the circuit has a breaker. A breaker protects against short circuits; it does not protect the motor from sustained overload, and a contactor cannot either.
- Setting the overload dial to the breaker or contactor rating. Set it to the motor FLC. An oversized setting means the motor can burn before the relay trips.
- Ignoring derating in hot panels. A contactor mounted beside other heat sources inside a closed enclosure carries less than its open-air rating.
- Forgetting auxiliary contact counts. If the hold-in circuit, pilot lights, and interlocking need more NO/NC contacts than the frame provides, retrofitting later is more expensive than ordering correctly.
Conclusión
A contactor for a motor starter is sized in three steps: read the motor FLC from the nameplate, choose a frame whose AC-3 rating covers that current, and pair it with an overload relay whose adjustable range brackets the FLC with the dial set to it. Get the coil voltage right for the control circuit, add mechanical interlocking for reversing duty, and the starter will switch reliably for years. When you are ready to spec the hardware, browse the CJX2-F series AC contactors and compare AC-3 ratings across the frames for your motor size.
PREGUNTAS FRECUENTES
What size contactor do I need for a motor starter?
Choose a contactor whose AC-3 current rating is at least equal to the motor’s full-load current. For example, a 7.5kW motor at 400V drawing about 15A typically needs an 18-25A AC-3 frame. Verify the FLC on the motor nameplate first.
Can a contactor protect a motor from overload?
No. A contactor is a switching device, not a protective device. Overload protection must come from a separate thermal or electronic overload relay that trips the contactor’s control circuit when the motor current stays too high.
What is the difference between a motor starter and a contactor?
A contactor is a single switching device. A motor starter is the assembly that switches and protects the motor, typically a contactor plus an overload relay, and often an enclosure and control devices.
Do I still need an overload relay if the circuit has a circuit breaker?
Yes. The breaker is sized for short-circuit protection and does not detect the moderate, sustained overloads that damage motor windings. A correctly set overload relay is the device that protects the motor itself.
What does AC-3 mean on a contactor?
AC-3 is the IEC utilization category for starting squirrel-cage motors and switching them off at running speed. A contactor’s AC-3 current rating is the value to use when selecting it for normal motor starter duty.
How do I set a thermal overload relay?
Set the current dial to the motor nameplate full-load current, or within the allowance permitted by your local code (commonly up to about 115-125% depending on service factor). Never set it by the breaker size or the contactor rating.



