This index routes a field symptom to its most likely cause and to the page with the full measurement procedure. It deliberately stays shallow: each row names the cause and the first check, then hands off to a dedicated guide. Troubleshooting pages that try to explain everything in one scroll bury the answer you came for.
Start with the five-minute triage below if you are standing in front of a panel right now. Use the symptom table if you already know what you are seeing and want the next step.
Five-Minute Field Triage

Work down the list in order and stop at the first match:
- Visible burning or melting? Replace the contactor. Do not re-energize it to “test” — a welded or carbonized pole can fail closed or phase-to-phase. This is the one symptom where diagnosis is over.
- No click when the control circuit is live? The fault is upstream of the contacts: control supply, control wiring, or the coil itself. Jump to the coil test guide.
- Humming, buzzing or chattering while pulled in? Three different sounds with three different causes — shading ring, pole face, or low coil voltage. The dedicated page on buzzing and chattering separates them by ear.
- Stays closed after the command drops out? Treat as welded contacts — a safety issue, not a nuisance. The safety contactor guide explains the feedback monitoring that catches this condition automatically.
- Trips on overload but the motor feels fine? Check the relay setting against nameplate FLC and the three-phase current balance before touching the contactor. The overload setting guide and the trip class comparison cover both.
The Symptom Index

| Symptom | Most likely cause | First check | Detail page |
|---|---|---|---|
| Contactor does not pull in | Open control circuit or dead coil | Coil voltage at A1–A2 under command | Coil test |
| Hums but does not seal | Coil voltage below 85 % of Uc | Voltage under load, not open-circuit | Coil voltage |
| Loud continuous hum when sealed | Worn shading ring or dirty pole face | Pole faces for rust, dust or debris | Buzzing fix |
| Chatters on and off | Intermittent control supply or loose terminal | Terminal torque and control wiring | Buzzing fix |
| Coil burnt or blackened | Overvoltage, jammed armature, wrong coil | Coil resistance against the rated band | Coil test |
| Contacts welded closed | AC-4 duty on an AC-3 frame, or a short circuit | Contact tip thickness; check downstream | Contact wear |
| One phase dead at the motor | Single pole eroded open | Pole-to-pole resistance delta | Contact wear |
| Overload trips on start | Relay dial set below nameplate FLC | Dial setting versus FLC | Overload setting |
| Overload trips in service | Single-phasing, bearing drag, ambient heat | Three-phase current balance | Overload setting |
| Overheating, discolored terminals | Loose termination or undersized cable | Thermal scan and torque check | Maintenance checklist |
| Contact wear in weeks | Frequent jogging or AC-4 duty | Operations count per hour | AC-3 vs AC-4 |
| Nuisance trips in a hot panel | No ambient compensation on the relay | Enclosure internal temperature | Derating guide |
If none of the twelve rows matches
Two fallbacks cover the rest. First, test the contactor as a component — the multimeter test procedure checks coil resistance, contact continuity and insulation step by step, and the no-instrument version in three diagnostic hacks works when the panel is dead. Second, confirm the symptom is not upstream: a VFD-driven motor that never starts may be the drive’s interlock logic, not the contactor — see contactor on VFD input vs output.
Repair or Replace: The Decision Line
Most contactor symptoms end in replacement, but the line is worth drawing precisely because parts and labor differ by frame size:
| 조건 | Action | Why |
|---|---|---|
| Welded contacts | Replace | Welding hardens the contact surface; the next weld comes sooner |
| Contact erosion past ~1/3 tip thickness | Replace contact set (large frames) or unit | Bounce and arcing increase once overtravel is gone |
| Burnt coil | Replace coil (if a genuine coil fits and the armature moves freely) | But first find why it burnt — see the coil test page |
| Broken or missing shading ring | Replace unit on small frames; ring on large ones | The hum returns and the armature runs hot until fixed |
| Discolored but sound housing and terminals | Clean, re-torque, re-test | Heat discoloration alone does not condemn the unit |
Whatever the repair, reset discipline applies: never reset an overload trip without measuring the running current first. The reset guide explains the three-strike rule and when a reset becomes the fault.
When It Is Not the Contactor
Two conditions routinely get blamed on the contactor and aren’t:
- Motor-side current imbalance: a failing motor winding or dragging bearing raises current on one phase; the overload relay trips, and the contactor takes the blame because it is visible. Measure at the contactor lugs, compare against the motor nameplate, and only then condemn a component.
- Control logic: interlocks, safety relays and PLC outputs command the coil. A contactor that “won’t pull in” with 0 V at A1–A2 is obeying instructions. The reversing wiring guide and the STO vs contactor safe-stop comparison cover the two most common logic traps.
For the preventive side — the inspections that catch most of these symptoms before they stop a line — the maintenance schedule lays out intervals by duty class, and the component anatomy guide explains what each part does when it fails.
Record What You Find, Even When You Fix It Fast
Field troubleshooting generates the data that makes the next failure cheaper. Three fields are worth writing down every time, in the work order or on the panel card:
- What the symptom actually was — in the operator’s words, not the eventual diagnosis. “Loud hum for two weeks before it stopped” is diagnostic gold that “replaced contactor” erases.
- What you measured — coil voltage, pole resistances, trip settings, running currents. The acceptance values live on the detail pages; the numbers themselves belong to your plant’s history.
- What was replaced and when — frame, brand, and hours in service. Two contactors from the same frame failing at similar hours points at duty or environment, not chance; the derating factors usually name the cause.
After three or four recorded events, patterns emerge that no single visit can show: the panel that runs hot every summer, the crusher that jogs too often, the pump that single-phases when the supply dips. Troubleshooting pages fix today’s fault; records fix the plant.
자주 묻는 질문
Where do I start if the panel is completely dead?
Measure coil voltage at A1–A2 while commanding the contactor. Zero volts means the problem is upstream; correct voltage with no pull-in means the coil or mechanism. That single measurement splits the search space in half — the coil test page continues from there.
Can I swap the contactor without checking anything else?
You can, and it often works — but a contactor that failed for a reason will fail the replacement too. Two minutes with the symptom index usually names the cause before the spare is out of the box.
How do I know if the overload relay or the contactor is at fault?
They fail differently: relays trip (a circuit decision), contactors fail to conduct or to release (a physical state). If the load runs and then trips, look at the relay; if it never starts or never stops, look at the contactor.
Why does my new contactor hum louder than the old one?
Usually a pole face that never seated during commissioning, or a coil voltage marginally below nominal. A brief hum at pickup is normal; continuous hum is a shading ring or voltage problem and shortens coil life.
Is it safe to keep running a contactor that chatters?
No. Chatter multiplies make-break arcs, erodes contacts fast and heats the coil. Isolate the cause the same shift — the buzzing page lists the three causes in the order to check them.
Which single spare should a small plant stock?
The frame that feeds the most critical motor, with its matching coil, plus one overload relay of the same setting range. The maintenance schedule page prioritizes spares by criticality if you need a fuller list.
